Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
12 Positions Transparent External Electric Meter Box Mcb Flame Resistant
The CAM168-B12 is equiped with a 225Amp main safety switch along with 20-40Amp MCBs for user safety precautions. It is designed as a cost-effective and affordable as well as durable meter box.It is intended for accommodation of 12 pieces single phase electric meters either prepayment or smart. It is made of reinforced Polycarbonate (PC) engineering plastic and Glass Fiber(GF). This box has over 500,000 installations in and out of China market and has a high reputation for its stability and durability. The CAM168-B12 is moisture-proof, impact resistant, anti-aging and corrosion, and UV-resistant, allowing to be installed in very severe environments. The sectional design of dividing meter from the MCB and main switch provides utmost safety to consumers and field technicians.
FUNCTIONS AND FEATURES:
a) BS footprint 5685 mounting
b) With wires and 12 P MCB and a main switch
c) Transparent PC material door
d) Flame resistant material
e) Housing of prepaid and smart meters
f) Rated IP 54 protection
g) With hinges, lock and key
h) Tamper sensor detects illegal intrusion
User Benefit
1) Easy installation and maintenance
2) Folded edges minimizing damages to users and cables
3) Double-hinged and removable box door adds convenience to daily maintenance
4) Operatable under all climate conditions
5) Rust protection and quality finish
6) Din Rail models available
Specifications:
Material |
PC+10%GF |
Display Window |
Transparent |
Keypad Operation |
Operable (operation can be disabled upon utility's order request) |
Safety Protection |
Operable breaker inside box |
Flame-Resistance |
Comply with requirements of 960 glow-wire test as per IEC60695-2-1 |
Fire Resistance Test |
UL94-V0 Rated@1.5mm |
Meter Installation |
BS 5685 |
Insulation Level |
No flashover and breakdown phenomenon under 50/60Hz sine wave 2000V/min |
Heat Dissipation |
Ventilation holes for cooling |
Tamper Protection |
Seals |
Climate Effect |
Meter box won't crack and deform under the below temperature changes: From high temp of 60±2for 4h to 20 From low temp of -30±3for 4h to 20 |
Compression Resistance |
Meter box won't crack and be damaged when a weight of 100kg with an area of 10×10cm² is put on the display window or any position for 3 minutes |
Impact Resistance |
With fixed screws tightening on the meter box, do the free-fall test from a height of 2m, the meter box is intact and shock resistant |
ShenzhenCalinmeterCo LTD [China (Mainland)]
Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)